Google Reveals Why Its Backup Generators Didn't Start During the October London Outage

Google Reveals Why Its Backup Generators Didn't Start During the October London Outage

Google Cloud has explained why its backup generators never started during the 20 October power failure in London that disrupted UK banks, Royal Mail and the courts. In an update to its service status page on 4 November 2026, the company said the outage at the europe–west2–b zone began with an external underground cable fault on the site’s primary utility feeder. The second, independent feeder was already out of service for planned repairs. Battery backup kept systems running for about five minutes — and then the generators, which should have taken over, never received the signal to start.

The reason, according to Google, was a “voltage–sensing design flaw and PLC misconfiguration”. The programmable logic controller that manages the generator plant incorrectly concluded that a healthy utility supply was still available, even though both distribution feeds were de–energised. No automatic start command was issued. When the batteries ran down, the critical load was lost.

It is a detailed and candid account, and it tells a story that every organisation relying on cloud services should take seriously. The site was designed so that no single fault could take it down. In practice, routine maintenance, a genuine cable failure and a software logic error lined up, and defences that looked robust on paper were defeated one after another.

~5 min
How long the UPS batteries kept systems running, as designed
6 days
Feeder B had been out of service for repairs before Feeder A failed (14 to 20 October)
2N
Power design with two fully duplicated, independent utility feeds
0
Start signals the generators received after both feeds went down

How the site was meant to work

The London facility uses what Google describes as a “2N” power architecture. In simple terms, everything is duplicated. There are two fully independent utility feeds, known as Feeder A and Feeder B, each capable of supporting the site. Behind them sits a central high–voltage generator bank, controlled by a dual–redundant programmable logic controller (PLC). Between the mains supply and the servers, uninterruptible power supplies (UPS) provide battery power for the short period needed for generators to start and take the load.

The design principle is that no single point of failure should ever take the site down. Lose one feeder, and the other carries the load. Lose both, and the UPS bridges the gap while the PLC tells the generators to start. Each layer is meant to cover the failure of the one before it.

What actually happened

The chain of events, as Google describes it, ran as follows.

During a routine quarterly generator load test, issues were identified that needed corrective repairs. To allow that work, Feeder B’s circuit breaker was deliberately opened on 14 October 2026. From that point, Feeder A alone was supporting the entire critical load. That is a normal, planned state during maintenance — the generators were still there as the backup.

On 20 October, Feeder A’s external underground cable, supplied by the site’s power company, developed a fault. With Feeder B already open, the site lost its utility supply. The UPS systems activated exactly as designed and kept everything running for about five minutes, which is the time they are built to cover.

The generators should have started within that window. They did not, because the PLC never told them to. A voltage–sensing design flaw combined with a misconfiguration caused the PLC logic to indicate that a healthy utility source was still available. As far as the controller was concerned, there was no emergency. When the UPS batteries were exhausted, the critical load was lost.

The effects reached far beyond the data centre. The outage disrupted Lloyds, HSBC, Barclays, NatWest, Royal Mail, Revolut and the Ministry of Justice’s court video platform, among others. Our original report on the day of the outage and the single–region problem set out how widely the disruption was felt.

Redundancy is only as strong as its least–tested link

The London site had two feeds, a generator bank, a dual–redundant controller and battery backup. On paper that is a robust design. In practice, one feed was out for maintenance, the other suffered a real fault and the controller’s logic failed to recognise what was happening. The same pattern applies to your own systems: a backup internet line that has never been tested, a server replica that silently stopped syncing, a cloud backup nobody has restored from. If you have not tested a failover recently, you do not know whether it works.

How the account fits with earlier reporting

At the time of the outage, UK Power Networks said its London electricity systems had run normally throughout. Google’s update now attributes the trigger to an external underground cable fault on the feeder supplying the site. The two statements are not necessarily in conflict: a fault on a single feeder cable serving one facility need not affect the wider distribution network. Either way, Google’s own account is clear that the outage resulted from the site’s failure to start its generators once the utility supply was lost, not from the cable fault alone.

The sequence, step by step

The timeline below is drawn from Google’s post–incident update and the reporting around it. Where no exact time was given, the step is described rather than timed.

Before 14 October 2026 — quarterly load test
A routine quarterly generator load test identifies issues that need corrective repairs.
14 October 2026 — Feeder B opened
Feeder B’s circuit breaker is deliberately opened to allow repairs. Feeder A now carries the entire critical load alone.
20 October 2026 — Feeder A cable fails
An external underground cable fault on Feeder A cuts the site’s remaining utility supply.
Immediately — UPS takes over
Uninterruptible power supplies activate as designed and keep systems running.
During the next five minutes — no start signal
The PLC incorrectly indicates that a healthy utility source is available, so no automatic start command goes to the generators.
After about five minutes — critical load lost
UPS batteries are depleted with no generator power to take over, and europe–west2–b goes down.
20 October 2026 — disruption spreads
Banks, Royal Mail, Revolut and the Ministry of Justice’s court video platform are among those affected.
4 November 2026 — root cause published
Google explains the failure, confirms the PLC has been reprogrammed and the changes tested, and commits to faster communications and wider failure testing.

What Google has changed

Google says it has reprogrammed the PLC logic to prevent the same failure mode from recurring, made further changes to the site’s electrical configuration and tested those changes to confirm they work as intended.

It has also committed to two broader follow–up actions:

  • A “Communications Enhancement”. Google will build an automated alert–to–communication mechanism for incidents that affect a whole location, so that customers are notified faster.
  • Expanded failure testing. Google will extend platform–wide testing of infrastructure–level failure scenarios beyond this specific site.

Both commitments address real weaknesses. Faster notification matters because, in an incident like this, customers can find out from their own users before any official update reaches them. And the fact that a latent logic error could sit undetected in a generator controller suggests that testing had not covered this precise combination of conditions. Whether the changes are enough will only be proven over time, but the direction is right.

Three lessons from the root cause

Maintenance quietly removes redundancy

For six days, the site was running on a single utility feed. That was deliberate, planned and entirely normal for maintenance — but it meant the site’s resilience rested on the generators working first time if anything happened to Feeder A. The same thing happens in every IT environment: a server taken offline for patching, a backup line disconnected during an office move, a replica paused during an upgrade. During those windows, you are less resilient than your design suggests.

1 of 2 feeds in service
From 14 October, with Feeder B opened for repairs, only Feeder A was supplying the site. When its external cable failed on 20 October, the generators were the last line of defence — and they never received a start signal.

Control logic can fail silently

The generators were physically available. The batteries worked. The failure was in the logic that decides when to act. A controller that wrongly believes everything is fine is in some ways worse than one that fails loudly, because nothing alerts anyone until it is too late. Software that monitors and switches systems — failover scripts, health checks, backup schedulers — deserves the same scrutiny as the systems it protects.

Test the combination, not just the parts

Each component was presumably tested. The quarterly load test, after all, was what identified the issues on Feeder B. But the specific combination — one feed open, the other failing, the controller misreading voltage — was not caught. Google’s commitment to expanded infrastructure–level failure testing recognises this. For smaller organisations, the equivalent is testing realistic scenarios end to end: not “does the backup exist?” but “can we restore from it on a bad day, with one system already down?”

What protects a business from a provider outage

No business can fix a cloud provider’s generator logic. What it can control is how much it depends on any one zone, region or provider, and how quickly it can recover. The chart below is our indicative assessment — not measured data — of how much each measure reduces a smaller UK business’s exposure to an outage like this one.

Independent backups held outside the primary provider
90%
Critical systems able to run in a second region or provider
84%
Restores and failovers tested at least twice a year
80%
Workloads spread across multiple zones in a region
62%
Documented continuity plan with manual workarounds
58%
Knowing which suppliers depend on which cloud regions
50%
Trusting the provider’s data centre redundancy alone
8%

The bottom bar is the assumption this incident challenges most directly. Google’s site was built with extensive redundancy, and it still failed. That is not a reason to distrust cloud providers — they generally run infrastructure far more reliably than most organisations could themselves — but it is a reason not to treat their redundancy as your continuity plan.

Multi–zone deployment sits in the middle for a reason. It protects against many failures, but our earlier coverage noted that the other London zones did not fully absorb the load on 20 October, and europe–west2 is Google’s only UK region. Independent backups and the ability to run elsewhere give more protection, especially for systems that must keep working.

A cloud resilience score card

The score card below rates common positions for UK businesses that depend on public cloud services, directly or through suppliers. It is a judgement framework for planning, not an audit.

Cloud outage resilience, November 2026
Backups stored with a separate provider or location Strong
Restore tested end to end in the last six months Strong
Critical workloads spread across zones Partial
Recovery time objectives agreed for key systems Partial
Supplier cloud dependencies understood Partial
All data and backups in one zone of one provider Weak
Failover designed but never tested Weak
Outage alerts depend solely on the provider’s status page Weak

The last row connects directly to Google’s communications commitment. Providers are working to notify customers faster, but businesses should not rely on that alone. Simple independent monitoring of your own key services will often tell you something is wrong before any status page does.

What resilience costs a smaller business

The figures below are indicative ranges for a smaller UK business that relies on cloud services for key systems. They are planning estimates rather than quotations, and they vary with data volumes and how systems are built.

MeasureIndicative one–off costIndicative ongoing costWhat it addresses
Cloud dependency and continuity review£750–£3,000Reviewed annuallyKnowing which systems and suppliers depend on which provider and region
Independent backup to a second provider or location£300–£1,500 to set up£30–£300 per month, depending on data volumeData remains recoverable if the primary provider or zone is down
Microsoft 365 or Google Workspace backup£0–£500 to set up£2–£5 per user per monthEmail and files protected outside the platform itself
Multi–zone deployment for critical applications£1,000–£8,000Additional hosting, often 20–60% moreSurvives many single–zone failures
Warm standby in a second region or provider£3,000–£20,000£200–£2,000 per monthAllows critical services to keep running during a regional outage
Scheduled restore and failover tests£500–£2,000 per testTwice a yearProves the plan works before it is needed
Independent uptime monitoring£0–£200 to set up£10–£100 per monthEarly warning without waiting for a provider’s status page

Not every business needs a warm standby. For many, independent backups, a tested restore process and a clear manual workaround for a day of disruption are proportionate. The right level depends on how long you can operate without a system, and what an hour of downtime costs.

Relying on the provider versus planning for its failure

Provider redundancy only

Common, and usually fine — until it is not

All systems and backups in one provider and region
Resilience assumed from the provider’s data centre design
No independent copy of critical data
Outage awareness depends on the provider’s status page
Recovery time set entirely by the provider
Continuity plan untested or non–existent

Planned for provider failure

What the London outage argues for

Backups held with a separate provider or location
Critical services able to run elsewhere if needed
Restores and failovers tested regularly
Independent monitoring of key services
Recovery time objectives agreed and achievable
Manual workarounds documented for a bad day

The left column is not careless. Cloud providers are extremely reliable most of the time, and building redundancy costs money. But the London outage shows that “most of the time” is not “all of the time”, and that even carefully engineered sites can fail in unexpected ways.

How prepared are smaller UK businesses?

The gauge below is our indicative estimate of how well a typical smaller UK business could keep working, or recover quickly, if its main cloud provider suffered an outage like the one on 20 October. It is a judgement based on the score card patterns, not a survey result.

30/100
Indicative cloud outage resilience of a typical smaller UK business

A score of 30 reflects how many smaller organisations use the cloud: as a single platform for everything, with backups inside the same service and a reasonable but untested assumption that the provider will handle any failure. The gap is not usually technology. It is planning and testing.

Run your own “Feeder B is already down” test

Google’s outage hit while one layer of protection was already out for maintenance. Ask the same question of your own systems: if one backup or failover route is unavailable, what happens when the main one fails? Then test it. Restore a real file, a mailbox or a database from your independent backup to a separate location, time how long it takes and note what went wrong. A restore you have done once is worth far more than a backup you have never touched.

Analysis: credit for candour, and a lesson in layered failure

Google deserves credit for publishing a detailed root cause. It would have been easy to stop at “a power issue”. Instead, the company has explained the maintenance state, the cable fault, the controller’s logic error and the five–minute UPS window, and it has said what it has fixed. That transparency helps customers understand their own risk.

The account also confirms something resilience engineers have long known: serious outages rarely have a single cause. Here, three separate conditions were needed — Feeder B open, Feeder A failing and the PLC misreading the situation. Any one of them alone would probably have been harmless. Together, they defeated a design that looked robust.

For UK businesses, the strategic question remains the one raised on the day. Europe–west2 is Google’s only UK region, and the other London zones did not fully absorb the load. Organisations with UK data residency requirements face a real trade–off between keeping data in the UK and spreading risk across regions. Our reports on local opposition to new UK data centres and the Azure ExpressRoute and VPN outage explore other angles of the same concentration risk.

The answer for most smaller businesses is not to abandon a provider. It is to hold an independent copy of what matters, know how long recovery would take and make sure that a bad day at one data centre does not become a bad week for the business.

At a glance

ItemDetail
IncidentPower failure at Google Cloud europe–west2–b, London, on 20 October 2026
Root cause published4 November 2026, on Google Cloud’s service status page
TriggerExternal underground cable fault on primary utility Feeder A
Second feedFeeder B deliberately opened on 14 October for repairs after a quarterly generator load test
Battery backupUPS kept systems running for about five minutes, as designed
Why generators did not startVoltage–sensing design flaw and PLC misconfiguration indicated a healthy supply was still available
ResultCritical load lost when UPS batteries were depleted
Organisations affectedLloyds, HSBC, Barclays, NatWest, Royal Mail, Revolut and the Ministry of Justice’s court video platform, among others
FixesPLC logic reprogrammed, electrical configuration changed and changes tested
Follow–up actionsAutomated alert–to–communication for location incidents; wider infrastructure failure testing
Lesson for businessesHold independent backups, test recovery and do not treat provider redundancy as a continuity plan

For related coverage, see our reports on the original London outage and single–region risk, the Azure ExpressRoute and VPN outage, UK data centre opposition and cloud capacity, the ConnectWise cloud backup breach and LINX LON2 and network resilience.

Keep an independent copy of what matters

We set up hybrid cloud backup for UK businesses, holding your data outside your primary provider, and test restores regularly — so an outage at one data centre never leaves you without your files, email or systems.

Talk to us about Hybrid Cloud Backup

Frequently asked questions

What caused the Google Cloud London outage?
Google says an external underground cable fault on the site’s primary utility feeder cut power while the second feeder was already out for repairs. The UPS ran for about five minutes, but the generators never received a start signal because of a voltage–sensing design flaw and PLC misconfiguration.
What is a PLC?
A programmable logic controller is an industrial computer that monitors equipment and automatically triggers actions. At this site, a dual–redundant PLC controls the generator bank and should start the generators when utility power is lost.
Why was one feeder already offline?
Feeder B’s circuit breaker was deliberately opened on 14 October 2026 to allow corrective repairs after issues were found during a routine quarterly generator load test.
What does “2N” power mean?
It means the power supply is fully duplicated. The London site has two independent utility feeds plus a central generator bank, designed so that no single point of failure should take the site down.
Did the batteries fail?
No. The UPS systems activated as designed and kept systems running for about five minutes, the time they are built to cover until generators take over. The problem was that the generators were never told to start.
Who was affected?
The outage disrupted Lloyds, HSBC, Barclays, NatWest, Royal Mail, Revolut and the Ministry of Justice’s court video platform, among others.
Has Google fixed the problem?
Google says it has reprogrammed the PLC logic, made further changes to the site’s electrical configuration and tested the changes to confirm they work as intended.
What else is Google changing?
It plans a “Communications Enhancement” to notify customers faster about location–wide incidents, and expanded platform–wide testing of infrastructure–level failure scenarios.
Should we move away from Google Cloud?
Not necessarily. Any provider can suffer outages. The more useful step is to hold independent backups, understand your dependencies and test how quickly you could recover or run elsewhere.
Is spreading across zones enough?
It helps against many failures, but on 20 October the other London zones did not fully absorb the load, and europe–west2 is Google’s only UK region. Independent backups and tested recovery plans provide stronger protection.

Test your recovery before you need it

Our team reviews your cloud dependencies, puts independent backups in place and runs regular restore tests, so you know exactly how long recovery takes — and that it works.

Talk to us about Hybrid Cloud Backup

Google’s generators were there, fuelled and ready. They simply never got the message. For every organisation, the takeaway is the same: redundancy you have not tested is a hope, not a plan.

Tags:Cloud BackupIT SupportVirtual CIOAzure
Cloudswitched

London-based managed IT services provider offering support, cloud solutions and cybersecurity for SMEs.

Cloudswitched Service

Hybrid Cloud Backup

Automated hybrid cloud backup and disaster recovery for UK businesses

More about this service
CloudswitchedHybrid Cloud Backup
020 3004 3450
Insights & guides

Latest from our blog

Structured Data and Schema Markup: A UK Business Guide to Winning Rich Results in Google Search in 2026
SEO5 Nov 2026

Structured Data and Schema Markup

Schema markup is structured code added to web pages that describes their content in a standard vocabulary search engines understand: this page is a product...

Read article
Website Redesign Planning: A UK Business Guide to Avoiding the Mistakes That Tank SEO Rankings During a Rebuild in 2026
Web Development4 Nov 2026

Website Redesign Planning

Treating website redesign SEO as an afterthought is the most reliable way for a UK business to lose the organic traffic it spent years building. The pattern is...

Read article
Virtual CIO Onboarding: A UK Business Guide to What the First 90 Days Should Actually Look Like in 2026
Virtual CIO3 Nov 2026

Virtual CIO Onboarding

Good virtual CIO onboarding looks, from the outside, surprisingly unglamorous. Many UK businesses sign a virtual CIO contract expecting a strategy presentation...

Read article
Network Capacity Planning: A UK Business Guide to Forecasting Growth Before Your Network Becomes the Bottleneck in 2026
Network Admin1 Nov 2026

Network Capacity Planning

Network capacity planning is the practice of knowing how much headroom each part of your network has, forecasting when growth will use it up, and acting before...

Read article
Office Downsizing and Consolidation: A UK Business Guide to Moving to a Smaller Office Without Losing IT Capability in 2026
IT Office Moves31 Oct 2026

Office Downsizing and Consolidation

Planning office downsizing IT is a different exercise from planning a normal office move, and treating it as a smaller version of one is where most problems...

Read article
Microsoft 365 Copilot Adoption: A UK Business Guide to Why Most Deployments Fail to Change How People Work in 2026
Microsoft 365 Copilot30 Oct 2026

Microsoft 365 Copilot Adoption

A workable Copilot adoption strategy starts from an uncomfortable fact: buying Microsoft 365 Copilot licences does not change how anyone works. The pattern in...

Read article
Microsoft 365 Copilot ROI: How UK Businesses Are Measuring Productivity Gains in 2026
Microsoft 365 Copilot29 Oct 2026

Microsoft 365 Copilot ROI

Most UK organisations that bought Copilot in 2024 and 2025 have reached their first or second renewal, and the question in the room has changed. Nobody is...

Read article
Penetration Testing for Web Applications: A UK Business Guide to OWASP Top 10 Testing and What a Web App Pen Test Actually Covers in 2026
Penetration Testing28 Oct 2026

Penetration Testing for Web Applications

Web application penetration testing examines the software your customers, staff and partners actually use your portal, platform, booking system or API to find...

Read article
Backup Encryption: A UK Business Guide to Protecting Backup Data at Rest and in Transit Without Locking Yourself Out in 2026
Cloud Backup27 Oct 2026

Backup Encryption

Backup encryption at rest and in transit is now standard across almost every backup product, and most UK businesses assume their backups are protected because...

Read article
Private Connectivity to Azure and AWS: A UK Business Guide to ExpressRoute and Direct Connect vs Public Internet VPN in 2026
Cloud Networking26 Oct 2026

Private Connectivity to Azure and AWS

Private cloud connectivity means linking your offices or data centre to Azure or AWS over a dedicated circuit Microsoft ExpressRoute or AWS Direct Connect...

Read article
Technology stack

Built on technology you can trust.

We design, run and secure your IT on proven, industry-leading platforms, including Microsoft 365 and Azure, Cisco Meraki, Cloudflare, AWS, BitDefender and SolarWinds, so your business stays secure, scalable and reliable.

  • SolarWinds
  • Cloudflare
  • BitDefender
  • AWS
  • Hono
  • SolarWinds
  • Cloudflare
  • BitDefender
  • AWS
  • Hono
  • Opus
  • Office 365
  • Microsoft
  • Cisco Meraki
  • Microsoft Azure
  • SolarWinds
  • Opus
  • Office 365
  • Microsoft
  • Cisco Meraki
  • Microsoft Azure
  • SolarWinds

Enquiry Received!

Thank you for getting in touch. A member of our team will review your enquiry and get back to you within 24 hours.